VESSELS
AMERICAN TECH. AEROSOL GENERATORS
NEW MILLENNIUM FIRE SUPPRESSION
REPLACEMENT FOR: Halons, ΗFC, CO², inert gas systems The most powerful, safe and efficient fire suppression system.
WITH AUTOMATIC ACTIVATION OR BY MEANS OF FIRE DETECTION PANEL
MICRO-K aerosol fire extinguishing systems
Tested & Listed to: UL 2127 Standard, MCA - Maritime and Coast Guard Agency- UK, Ministry of Defence-Royal British Navy, Defence Procurement Agency-UK, Fire Protection Association-UK, N.F.P.A. - National Fire Protection Association LLOYD'S Register Quality Assurance
 |
|
SPECIAL CHARACTERISTICS
1. Simple Installation inside the fire-protected space. No piping, no cartridges etc. 2. Less agent needed. Only 50 - 100 grams of agent are required to protect a space of one cubic meter. 3. No pressurized- having no danger of casual desperation. 4. Easily applicable to any existing fire protection systems, in case of extension. 5. With +10 years of service life, requiring a minimum of maintenance and no refilling. 6. Autonomous Installation with no need of electric current. Activation by means of a breakable thermo-detection sensor, in preset temperature. 7. Non corrosive, non toxic, non oxidizing. 8. People and environment friendly. Non oxygen consuming.
|
 |
| |
 |
|
 |
Underwriters'
Laboratories of Canada |
|
APPLICATION AREAS
- Vessels - Vehicles - Small Aircrafts - Railway Locomotives - Electric Trains
- Inflammable materials stores / Paint Stores Control Rooms / Computer & Server Rooms
- Tele-channels, Cellular Industry, Unmanned Nodes for Telecom Industry
- Laboratories Optic fibre tunnels / Cable Channels / False ceiling / False floors
- Industrial production areas Rotary press Machines
- Power Substations of Low and Medium Voltage Transformer rooms
- Machinery spaces (Plants, vessels, vehicles) Tank Stations / Pumping Rooms, Natural Gas Stations
- IPS - UPS - Electrical Panel Rooms
 Basic Diagram
OPERATION
- Installation in the machine compartment of the vessel
- Connection with the thermo-sensor and the actuation button / signal, in the captain's cabinet
- In case of fire, automatic activation via the thermo-sensor / or manually, via the button
- Aerosol formation in the machine compartment of the vessel (non toxic, non corrosive), produced by potassium salts
- Immediate cut of the chain reaction of the flame and rapid, total extinguishment
|
Technical Characteristics |
| Solid material chemical composition |
|
| Potassium nitrate |
75 mass % CAS No 7757-79-1 |
| Epoxy resin polymer |
23 mass % CAS No 25068-38-6 |
| Magnesium |
2 mass % CAS No 7439-95-4 |
| Basic rate of solid material per m³ |
100 g/m3 |
| Duration of extinguishing effect |
+ 30 min |
| ODP |
0 |
| GWP |
0 |
| Obscuration |
high |
| Toxicity |
low |
| Storage temperature |
from - 40°C to + 54°C |
| Humidity of installation space |
0-98 % |
| Conductivity |
none up to 24000V |
| Service life |
+10 years |
| Generator |
Micro K SC |
Micro K 1,1 |
| Solid material weight, g |
600 |
1,100 |
| Generator weight, g |
3,700 |
7,000 |
| Max volume m³ |
5,3 |
9,4 |
| Length, mm |
269 |
310 |
| Diameter, mm |
160 |
183 |
| Discharge time, sec |
< 20.0 |
< 25.0 |
|